TE Technology TC-24-10 User Manual

Page 16

Advertising
background image

16

3.8

Double the bandwidth calculated in section 3.6, and then adjust the Proportional Bandwidth Potentiometer 
to  this  new  value.    Fully  counterclockwise  =  0.5  °C,  and  fully  clockwise  =  5  °C.    Each  full  turn  of  the 
Proportional Bandwidth Potentiometer corresponds to 0.18 °C increment.  If doubling the bandwidth yields 
a value greater than 5 °C, set the bandwidth to 5 °C. 

3.9

Calculate the inverse, or reciprocal, of the natural period recorded in section 3.7, and adjust the controller 
Integral  Rate  (the  number  of  repeats  per  minute)  to  this  value.    Each  full  turn  of  the  Integral  Rate 
Potentiometer corresponds to 0.102 repeats per minute increment. 

3.10 These Proportional and Integral settings are approximate settings and may need further minor adjustments.  

Record  the  final  number  of  turns  used  on  the  Proportional  Bandwidth  Potentiometer  and  Integral  Rate 
Potentiometer. 

 

Final  number  of  turns  on  the  Proportional  Bandwidth  Potentiometer  =__________________  from 
maximum clockwise. 

 

Final  number  of  turns  on  the  Integral  Rate  Potentiometer  =__________________  from  maximum 
counterclockwise. 

 

Additional systems with the same thermodynamic properties will operate using the Potentiometer settings 
listed above. 

 

Tuning Example

 

A. Suppose  that  16  counterclockwise  turns  of  the  Proportional  Bandwidth  Potentiometer  (R2)  were 

required  to  just  sustain  a  temperature  oscillation.    This  corresponds  to  a  proportional  bandwidth  of 
about (5 °C – 0.18 °C/turn x 16 turns =) 2.1 °C. (Reference section 3.6) 

 
B. It was then observed that the natural period of this oscillation was 2 minutes.  (Reference section 3.7) 

 
 

C. The Proportional Bandwidth Potentiometer (R2) should be adjusted to double the bandwidth to 4.2 °C.  

(Reference section 3.8)  This is about 20.5 turns clockwise from the full counterclockwise position (0.5 
°C + 0.18 °C/turn x 20.5 turns = 4.2 °C). 

 
 

D. The Integral Rate variable should be set to the inverse of the natural period by adjusting the Integral 

Rate  Potentiometer  (R8).    This  is  1/(2  min)  =  0.5  repeats  per  minute.    Since  each  turn  of  the 
potentiometer  equals  0.102  repeats  per  minute,  the  potentiometer  should  be  adjusted  4.9  turns 
clockwise from the full counterclockwise position. (Reference section 3.9) 

 
 

 

 

Advertising