Operating instructions – TE Technology TC-24-10 User Manual

Page 8

Advertising
background image

8

Regardless of whether you use one or two power supplies, when making a cooling system from a single TE module, 
the maximum operating voltage for that system is usually no more than 75% of the rated Vmax of the TE module.  
The 75% rule is based on the TE module being thermally connected to a “good” heat sink; system modeling should 
be  done  to  verify  this  rule  is  applicable  though.  If  multiple  TE  modules  are  used  in  a  series  or  series‐parallel 
combination, the Vmax of the system will be approximately 75% of the rated Vmax of each TE module multiplied 
by the number of modules in series. 
 

Operating Instructions 

1.0  Setup 

 

Portions  of  the  temperature  controller  (the  aluminum  frame  near  the  output  transistors,  for 
example) could exceed 60 °C during normal operating conditions. Temperatures greater than 60 °C 
can  result  in  a  hazard  to  the  user.  Use  caution!    Protect  against  accidental  contact  with  hot 
surfaces.  

If  the  temperature  controller  is  to  be  used  under  conditions  such  that  its  surface  temperatures 
could  possibly  exceed  60  °C,  test  the  surface  temperatures  under  the  worst‐case  operating 
conditions  of  maximum  ambient  temperature  and  highest  output  current  and  voltage.    If  any 
portion  of  the  temperature  controller  exceeds  60  °C  place  adequate  guards  around  the 
temperature controller to prevent contact with any hot surfaces. 

NOTE:  the maximum allowable ambient temperature for the controller is 50 °C.  Furthermore, the 
maximum allowable temperature of the controller base (underneath the transistor‐mounting area) 
is  90  °C.  Furthermore,  the  controller  might  need  additional  heat  sinking,  depending  on  ambient 
conditions and how much current is being drawn by the TE device. 

 

Note:    See  “Controller  Wiring  Diagram  (One  Power  Supply  Setup)”  or  “Controller  Wiring  Diagram  (Two 
Power Supplies Setup)”
 for additional reference. 
 

1.1

Set the position of jumper JP1. 

 To set the controller in cooling mode:  JP1 is shorted (jumper is installed) 
 To set the controller in heating mode:  JP1 is open (jumper is removed) 

1.2

Attach the thermistor at an appropriate temperature‐control location.  Locating the thermistor at the cold 
side of the TE device provides better control stability than locating it at the object, liquid, or air that is to be 
cooled/heated. However, in doing so, there will be a temperature difference between the TE device and the 
object, liquid, or air that is to be cooled/heated.  The temperature set point can be adjusted to compensate 
for this temperature difference if necessary. 

NOTE:    When  possible,  it  is  recommended  that  at  least  50  mm  of  the  thermistor’s  wire  be  thermally 
connected to the cold side of the TE device.  This can be accomplished by placing aluminum tape over the 
thermistor  wires  and  adhering  the  wires  and  tape  to  the  cold  side  of  the  cooler.    If  this  is  not  done,  the 
thermistor wires will be at a different temperature than the cold side and they will add or remove heat in 