2 no action, 2 analog output – Tecfluid MT03L User Manual

Page 20

Advertising
background image

20

Example 1
If the activation point is programmed to 100 cm and the deactivation point is programmed
to 90 cm, when the level is zero the output will be deactivated. When the level reaches a
value of 100 cm the output will be activated until the level falls below 90 cm.

Example 2
If we program an activation point of 90 cm and a deactivation point of 100 cm, when the
level is zero the output will be activated. When level reaches a value of 100 cm the output
will be deactivated until the level falls below 90 cm.

7.5.1.2 No action

The relay will be always at rest.

7.5.2 Analog

output

The level value corresponding to 4 mA and 20 mA can be programmed and the calibration

for these two values can be made as well.