Interface specifications

* To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m

boundary to the rails and connected to this port.

The cable shield should be properly connected (360°) to an earthing point within 1 m from this port. This earthing

point should have a low impedance connection to the conductive enclosure of the apparatus cabinet, or similar,

where the unit is built-in. This conductive enclosure should be connected to the earthing system of an installation

and may be directly connected to the protective earth.

Power LV
Rated voltage

12 to 48 VDC

Operating voltage

10 to 60 VDC

Rated current

250 mA @ 12 VDC
125 mA @ 24 VDC
63 mA @ 48 VDC

Rated frequency

DC

Maximum inrush
current @ 10 ms

0.3 A²s @ 48 VDC

Polarity

Reverse polarity protected

Redundant power input

Yes

Isolation to

All other 2 kV

rms

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm² (AWG 24 – 12)

RS-422/485
Electrical specification

EIA RS-485
2-wire or 4-wire twisted pair

Data rate

300 bit/s – 115.2 kbit/s

Data format

7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits

Protocol

Transparent, optimised by packing algorithm

Retiming

Not applicable

Turn around time

< 3 bits

Circuit type

TNV-1

Transmission range

≤ 1200 m, depending on data rate and cable type (EIA RS-485)

Settings

120 Ω termination and fail-safe biasing 680 Ω

Protection

Installation Fault Tolerant (up to ±60 V)

Isolation to

Power 2 kV
Ethernet 1; 1.5 k V

rms

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm² (AWG 24 – 12)

Shielded cable

Not required, except when installed in Railway applications as
signalling and telecommunications apparatus and located close to
rails*

Conductive housing

No