Large Dehumidifying Dryers

Maintenance

87

5-3 Corrective Maintenance

Symptoms of Worn Out Desiccant

The moisture adsorption capacity of the desiccant used in Large Dehumidifying Dryers
degrades after an indefinite period of time. Useful life depends on variables such as material
moisture content, plasticizer vapors in the return air and number of regeneration cycles.

Your dryer may need new desiccant if it exhibits any of the following symptoms:

• The plastic material is not being dried sufficiently (high scrap/reject rate).
• The air temperature at the top of the regenerating desiccant bed rapidly climbs to

350°F or more shortly after the start of regeneration, even though a saturated bed has
just started heating.

• The process air dewpoint, measured with a portable dewpoint monitor, is higher than

-10°F throughout the process drying cycle.

• Smoke or dust is being blown out of the process air outlet.
• Noticeable amounts of desiccant in the beds is a medium-brown color, or darker.

If any of these signs are noticed, the desiccant in the desiccant beds should be replaced.
Desiccant replacement kits are available from the Parts Department. If you wish, the
desiccant beds can be repacked at your site by a service technician.

WARNING! DESICCANT MATERIAL CAUSES EYE IRRITATION

BREATHING MAY BE HARMFUL/MAY CAUSE SKIN IRRITATION!

Do not get in eyes.
Avoid prolonged contact with skin.
Use with adequate ventilation.
Wash thoroughly after handling.

FIRST AID:
In case of eye contact, immediately flush eyes with plenty of water for
at least 15 minutes. If irritation persists, see a physician.

Replacing the Desiccant

Follow the procedure below to change the desiccant. See Figure 14 below for desiccant
tower components.

1. Disconnect electrical power to the dryer.
2. Remove the bolts and nuts securing the covers of each desiccant canister. Remove

the covers and set them aside.

3. With a shop vacuum that has a 4 micron HEPA filter, carefully remove all desiccant

from each tower.

4. Inspect all screens for tears or burn-through spots.
5. Fill each canister with 13X, 8 x 12 bead desiccant.