Replacing a Fan Module

You can replace a failed fan module while the storage chassis is powered up.
However, you must complete Steps 2 through 5 within two minutes to avoid thermal
shutdown of the storage chassis. Before you remove the fan module, make sure that
you understand all the steps in the following procedure.

IMPORTANT

To avoid thermal shutdown of the storage chassis, never

operate it for more than two minutes with the fan module removed or in the open
position.

To replace the fan module:

1. Unpack the replacement fan module and place it within reach of the storage

chassis.

2. Open the fan module.

3. Remove the fan module as shown below.

Removing the fan module

Cutout

Tab

Latch

Hinge pin

Mounting

bracket

Fan module’s
power/control

cable

Printed

circuit

board

A.Disconnect fan module’s
power/control cable.

C.Lift module free of hinge
pins and release latch.

B.Press module’s latch and
guide tab through cutout.