3 adjusting the reference offset, Important – Yaskawa Sigma II Series SGMVH User Manual

Page 245

Advertising
background image

8 Operation

8.7.3 Adjusting the Reference Offset

8-64

8.7.3 Adjusting the Reference Offset

(1) Automatic Adjustment of the Torque Reference Offset

When using torque control, the servomotor may rotate slowly even when 0 V is specified as the analog reference
voltage. This occurs when the host controller or external circuit has a slight offset (measured in mV) in the refer-
ence voltage. In this case, the reference offset can be adjusted automatically and manually using the panel oper-
ator or digital operator.
The automatic adjustment of analog (speed, torque) reference offset (Fn009) automatically measures the offset
and adjusts the reference voltage.
The SERVOPACK performs the following automatic adjustment when the host controller or external circuit has
an offset in the reference voltage.

After completion of the automatic adjustment, the amount of offset is stored in the SERVOPACK. The amount of
offset can be checked in the manual adjustment of torque reference offset (Fn00B).
The automatic adjustment of analog reference offset (Fn009) cannot be used when a position loop has been
formed with the host controller and the error pulse is changed to zero at the servomotor stop due to servolock.
Use the torque reference offset manual adjustment (Fn00B).

The analog reference offset must be automatically adjusted with the servo OFF.

Use the following procedure for automatic adjustment of the torque reference offset.

Offset

Torque
reference

Reference voltage

Reference voltage

Offset automatically
adjusted in SERVOPACK.

Automatic
offset
adjustment

Torque
reference

IMPORTANT

Step

Display after

Operation

Digital

Operator

Panel

Operator

Description

1

Turn OFF the SERVOPACK, and input the 0-V reference voltage
from the host controller or external circuit.

2

Press the DSPL/SET or MODE/SET Key to select the utility
function mode.

3

Press the LEFT/RIGHT or UP/DOWN Key, or UP or DOWN
Key to select parameter Fn009.
*The digit that can be set will blink.

4

Press the DATA/ENTER Key once, or DATA/SHIFT Key for
more than one second. “rEF_o” will be displayed.

5

Press the DSPL/SET or MODE/SET Key.
The reference offset will be automatically adjusted.
When completed, “donE” will blink for about one second.

6

About one second later

After “donE” is displayed, “rEF_o” will be displayed again.

7

Press the DATA/ENTER Key once, or DATA/SHIFT Key for
more than one second to return to the Fn009 display of the utility
function mode.

Servo-

motor

Slow rotation
(Servo ON)

SERVO-
PACK

Servo OFF

0-V speed
reference or
torque
reference

Host
controller

(DSPL/SET Key)

DSPL

SET

MODE/SET

(MODE/SET Key)

(DATA/ENTER Key)

DATA

ENTER

DATA/

(DATA/SHIFT Key)

(Press at least 1 s.)

(DSPL/SET Key)

DSPL

SET

MODE/SET

(MODE/SET Key)

(DATA/ENTER Key)

DATA

ENTER

DATA/

(DATA/SHIFT Key)

(Press at least 1 s.)

Advertising