Figure 2-6, Generator Run Sense Options

Option 3 – Use an external 120VAC coiled relay to bring the generator's battery voltage to

the AGS run sense port (AGS Terminal Block Port #2) only while the generator is running.

The generator’s battery voltage must be 10 to 40 VDC.

120VAC Coil Relay

On Generator

NC

COM

NEU

HOT

NO

120VAC Outlet

Inside Generator

Generator

Battery

negative

run sense

AGS Terminal Block Ports:

1

2

3

4

5

6

7

8

DC Fuse

(5A max)

Option 1 - Tap into the positive side of the generator’s hour meter or running light; ensure

the voltage is 10 to 40 VDC only while the generator is running.

Generator

Battery

Inside Generator

Generator

Running Lamp

OR

Generator

Hour Meter

0

1

2

3

negative

DC Fuse

(5A max)

run sense

AGS Terminal Block Ports:

1

2

3

4

5

6

7

8

Option 2 - Use a 120VAC to 12VDC step-down transformer (normally used to charge power

equipment batteries) and plug into the generator’s 120VAC output. The step-down

transformer provides 12 VDC output only while the generator is running.

negative

DC Fuse

(5A max)

run sense

AGS Terminal Block Ports:

1

2

3

4

5

6

7

8

On Generator

120VAC Outlet

120VAC IN

12VDC OUT

TRANSFORMER

What if my generator does not have a run sense output? If your gen-

erator is not equipped with a generator run sense output, review Figure 2-6

for alternative options.

Option 3 – Use an external 120 VAC coiled relay to bring the generator’s battery voltage

to the AGS run sense port (AGS Terminal Block Port #2) only while the generator is

running. The generator’s battery voltage must be 10-40 VDC.

Option 2 – Use a 120 VAC to 12 VDC step-down transformer (normally used to charge

power equipment batteries) and plug into the generator’s 120 VAC output. The step-

down transformer provides 12 VDC output only while the generator is running.

Option 1 – Tap into the positive side of the generator’s hour meter or running light;

ensure the voltage is only 10-40 VDC while the generator is running.