Installation, Venting – CarAlarms.com P90-NG1 User Manual

Page 11

Advertising
background image

Excalibur

®

P90 Zero Clearance Direct Vent Gas Fireplace

11

VENTING

FPI Direct Vent System (Flex) Horizontal Terminations Only

These venting systems, in combination with the P90 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by
Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the "Exterior Vent
Termination Locations" section.

FPI Direct Vent (Flex) System Termination
Kit (Part # 946-515) includes all the parts
needed to install the P90 with a maximum
run of 4 feet.

1) 6-7/8" dia. fl exible liner (4 ft. length)
2) 4" dia. fl exible liner (4 ft. length)
3) spring spacers (4)
4) thimble

(2)

5) AstroCap termination cap (1)
6) screws

(12)

7) tube of Mill Pac (1)
8) plated

screws

(8)

9) screws #8 x 1-1/2" Drill Point, Stainless

Steel (4)

If a longer run is needed, the FPI Direct Vent
system (Flex) kit is 946-516 which includes
all the parts needed to install the P90 with
a maximum 10' run.

1) 6-7/8" dia. fl exible liner (10 ft. length)
2) 4" dia. fl exible liner (10 ft. length)
3) spring spacers (7)
4) thimble

(2)

5) AstroCap termination cap (1)
6) screws

(12)

7) tube of Mill Pac (1)
8) plated

screws

(8)

9) screws #8 x 1-1/2" Drill Point, Stainless

Steel (4)

Notes:
1) Liner sections should be

continuous without any joints or
seams.

2) Only Flex pipe purchased from FPI may

be used for Flex installations.

3) Horizontal vent must be supported every

3 feet.

INSTALLATION