Excalibur

®

P90 Zero Clearance Direct Vent Gas Fireplace

12

INSTALLATION

EXTERIOR VENT TERMINATION LOCATIONS

A=

Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)

B=

Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)

C=

Clearance to permanently closed window *(min. 12"/30cm)

D=

V

ertical clearance to ventilated soffi

t located above the terminal within a horizontal

distance of (24"/60cm) from the centerline of the terminal (min. 18"/46cm) check with

local code.

E=

Clearance to unventilated soffi

t

(min.

15"/38cm)

F=

Clearance to outside corner: with

AstroCap

T

e

rmination Cap (min 6"/15cm), with Dura-

V

ent

T

e

rmination Cap (14"/36cm)

G=

Clearance to inside corner: with

AstroCap

T

e

rmination Cap (min 6"/15cm), with Dura-

V

ent

T

e

rmination Cap (12"/30cm)

H=

Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally

from the centerline of the regulator

.

J=

Clearance to service regulator vent outlet *(min 36"/90cm)

K=

Clearance to non-mechanical air supply inlet to building or the combustion air inlet to

any other appliance *(12"/30cm) #(9"/23cm)

L=

Clearance to a mechanical air supply inlet *(min. 72"/1.8m)

#3' (91cm) above if within 10' (3m) horizontally

.

M=

Clearance above paved sidewalk or a paved driveway located on public property

*(min. 84"/2.1m)

N=

Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)

Note:

-

A

vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings a

nd serves both dwellings.

- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl

oor

.

- If the vent termination is accessible, a certifi

ed guard shall be installed.

*

As specifi

ed in CGA

B149 Installation Code. Note: Local codes or regulations may require dif

ferent clearances.

# In accordance with the current

ANSI Z223.1/NFP

A

54, Natioinal Fuel Gas Code.