Installation – CarAlarms.com P90-NG1 User Manual

Page 19

Advertising
background image

Excalibur

®

P90 Zero Clearance Direct Vent Gas Fireplace

19

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

FPI DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90

o

elbow (two 45

o

elbows equal one 90

o

elbow).

All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter

FPI Flex Vent
4" inner diameter
6-7/8" outer diameter

Note: Must use optional rigid pipe adaptor (Part # 510-

994) when using Rigid Pipe.

• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.

A vent guard (Part# 946-506/P) should be used
whenever the termination is lower than the
specifi ed minimum or as per local codes.

Note: FPI Direct Vent System (Flex) is only approved

for horizontal terminations.

All Rigid Pipe Systems
5" inner diameter
8" outer diameter

Note: Must use FPI increaser starter collar

(Part # 946-605) at beginning of vent run.

5" x 8" venting starts at unit.

Please note that all vertical
measurements are taken from
the base of the unit excluding
risers or bottom stand-offs.