P90 Zero Clearance Direct Vent Gas Fireplace

9

INSTALLATION

Fireplace

Stand

No hearth is
required when

the unit is raised

3" (76mm) off of
the floor surface

Flooring

HEARTH REQUIREMENTS

Floor Mounted Fireplaces

Raised Fireplaces

FACING REQUIREMENT

This fi replace requires a non-combustible material extending from the
framing header and sides.

The fl anges on the front face of the fi replace are for a facing thickness
of 1" (25mm).

Facing Over 1" (25mm) Thick

If the facing material is over 1" (25mm) thick (example: brick or river
rock), install the facing around the perimeter of the face. You may wish
to make a face template as shown on the diagram.

FPI offers a cover plate
template. See next page.

NOTE: If using a brick
hearth, the fi replace will
need to be raised to
accommodate the brick
thickness. Example: If the
brick is 2" thick, the unit
must be raised 1".

Note: 4 8 " ( 1 1 2 1 9 m m )

i s t h e m i n i m u m
height for both fl ex
termination or Rigid
Pipe venting.

4) Note: The unit does not

have to be completely
enclosed in a chase. The
clearance on top of the
unit is 0" to the standoffs
so combustible building
materials can be laid
directly on top of the
standoffs. You must
maintain clearance from
the vent to combustible
m a t e r i a l s f o r b o t h
rigid and fl ex, see the
"Clearances" section.

Yo u m u s t t a k e i n t o
account the depth of the
floor covering (carpet,
tile, linoleum, etc.) when
determining the height of
the fi replace stand.

The HeatWave Duct Kit has different
clearance and framing requirements, check
the HeatWave manual for details.

Please note that all vertical measurements are taken from the base
of the unit excluding risers or bottom stand-offs.