Installation – Emerson 1F92 User Manual

Page 17

Advertising
background image

15

Installation

this digital thermostat. As config-
ured at the factory, this thermostat
will maintain an accurate tempera-
ture. No further adjustment is
necessary, although you can use
these menu items to customize the
performance of the thermostat to
your requirements.

The adjustment range for HEATING
is from 1 to 40 (9 to 40 for heat
pump). The factory preset is 5 (13
for heat pump). The adjustment
range for COOLING is from 9 to
40. The factory preset is 12 (13 for
heat pump). The cooling will not go
below 9 because compressors
require a longer cycle. The adjust-
ment range for AUXILIARY (heat
pump only) is from 1 to 40. The
factory preset is 6.

The chart below shows how this adjustment range affects thermostat
performance.

HEATING

COOLING

Anticipation Value

Cycle Length Differential Temperature

Cycle Length Differential Temperature

Shorter

0.4–0.6 F (0.2–0.3 C)

N/A

1–8

N/A

Longer Shorter

9–20

0.6–1.0 F (0.3–0.6 C)

0.6–1.0 F (0.3–0.6 C)

Hydronic Longer

21–40

1.0–1.6 F (0.6–0.9 C)

1.0–1.6 F (0.6–0.9 C)

These numbers are approximate and represent operation with a typical
system. Actual temperature differentials and run times may vary widely
based on your building and equipment, as well as outdoor temperature
conditions.