EMI Volts/HZ/pH User Manual

Page 10

Advertising
background image

www.enviromaster.com

Side Discharge Condensers

10

inStallation inStrUCtionS

9. Refer to Charts on page 12 to “fine

tune” the refrigerant charge to meet

your conditions.

reFrigerant proCeSSing

Complete piping ConneCtionS

important noteS:

1. To find the charge adjustment and system charge for any evaporator and tubing length:

Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Charge + Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.

8. Charge to proper weight, charge

based on feet of interconnect (tables

starting on page 10).

S1C reFrigerant CHarge table

ConDenSer

eVaporator pairing

line CHg/Ft

FaCtorY CHarge

S1C9

CAH12

.25 oz.

37 oz.

S1C2

CAH12

.25 oz.

40 oz.

S1C8

CAH24

.56 oz.

51 oz.

S1C4

CAH24

.56 oz.

65 oz.

S1C3

CAC36

.56 oz.

72 oz.

S1C6

CAC36

.56 oz.

90 oz.

S1C9

WLH09/UNH09

.25 oz.

37 oz.

S1C2

WLH12/UNH12

.25 oz.

40 oz.

S1C8

WLH24/UNH24

.56 oz.

51 oz.

S1C4

WLH24/UNH24

.56 oz.

65 oz.

S1C3

WLC30/UNC36

.56 oz.

72 oz.

S1C6

WLC36/UNC36

.56 oz.

90 oz.

S1H (Heat pUmp) reFrigerant CHarge table

ConDenSer

eVaporator pairing

line CHg/Ft

FaCtorY CHarge

S1H9

WLH09/UNH09

.25 oz.

41 oz.

S1H2

WLH12/UNH12

.25 oz.

44 oz.

S1H8

WLH24/UNH24

.56 oz.

53 oz.

S1H4

WLH24/UNH24

.56 oz.

67 oz.

Note:

Charging should be done with a dial-a-charge or weighed in with a scale.