inStallation inStrUCtionS

reFrigerant piping

Continued

2. Protect the valves by wrapping with a

wet rag "heat sink" before brazing.

3. We recommend the use of a shield (can

be made from some scrap metal) to

protect the paint.

4. Braze tubing into fittings.

1. Clean the ends of tubing and insert into

fittings.

5. Attach manifold set.

6. Evacuate line to 500 microns or less to

ensure all moisture has been removed

and there are no leaks.