The units are delivered precharged

with refrigerant for the condenser coil

and the evaporator. Charging of the field

installed piping is required. Refer to the

refrigerant charge table for the proper

amount to be added for the applications

interconect piping. Unit service valves are

solid brass, for sweat connections.

important:

All systems require

field charge adjustments. Refer to the

"Refrigerant Charge Tables" for proper

weight charge and to the supplied

"Operational Charts" for proper system

pressures and temperature at different

outdoor conditions. Superheat should

be used for final system charge.

When charging and checking pres-

sures/temperatures on system supplied
with low ambient option, the fan cycle
switch should be jumped out of the circuit
temporarily to obtain accurate data.

inStallation inStrUCtionS

reFrigerant proCeSSing

Continued

S2C reFrigerant CHarge table

ConDenSer

eVaporator pairing

line CHg/Ft

FaCtorY CHarge

S2C99

WLH09

.25 oz.

28 oz./ 28 oz.

S2C22

WLH12

.25 oz.

33 oz./ 33 oz.

S2C92

WLH09+WLH12

.25 oz.

28 oz./ 33 oz.

S2C99

CAC12

.25 oz.

28 oz./ 28 oz.

S2C22

CAC12

.25 oz.

33 oz./ 33 oz.

S2C92

CAC12

.25 oz.

28 oz./ 33 oz.

S2C99

UNH09

.25 oz.

28 oz./ 28 oz.

S2C22

UNH12

.25 oz.

33 oz./ 33 oz.

S2C92

UNH09+UNH12

.25 oz.

28 oz./ 33 oz.

Warning

it is illegal to discharge refrigerant
into the atmosphere. Use proper re-
claiming methods & equipment when
installing or servicing this unit.

Note: The following air handlers are equivelent in electrical specifications

and system combinations.

WLH09 = UNH09

WLH12 = WLH12

WLH24 = UNH24

WLC30 = UNC36