operation anD maintenanCe

The S1C/H and S2C outdoor sections

are the compressor bearing units of the

system. It operates at the command of
the indoor section or room thermostat.

Therefore, the system operation will be

described in the manual pertaining to the
indoor section.

EMI units are designed and con-

structed for reliability and long life with
minimal maintenance. You can assure

peak operating efficiency by regularly

inspecting for free air passage into and

through the coil. If debris collects on the air

coil, it should be cleaned by "back-flushing"

with a spray of water or vacuuming. TURN
OFF POWER SUPPLY FIRST.

Outdoor

units may be cleaned or waxed if desired.

Use a non-abrasive car wax (on metal

surfaces only).

This unit is equipped with a perma-

nently lubricated motor. Although oiling is

not necessary, adding a few drops through

the oiling ports twice yearly will extend the

life of the motor. Do not over oil.

Panels should remain on the unit at all

times. Service should be performed by a
QUALIFIED

service agency only.

SpeCiFiC CHangeS

All EMI products are subject to on-

going development programs so design

and specifications may change without

notice. Please consult the factory for more

information.

Starting tHe Unit

• In low ambient cooling 9-12 Btuh units,

if a crankcase heater is installed,

power the system 24 hours before

attempting to start the unit in cool

weather (below 60° F).

• After doing a final system check using

the Operation Charts (supplied on pre-

vious pages). Record results on Test

Unit Data Sheet on page 26.

preperation For Start-Up

• Remove gauge set. Mount all access

panels and make sure they are prop-

erly secured.

• Make final visual inspection and repair

any deficiencies.

note:

A hard start kit may be required

for units in low voltage applications.

Single-Zone anD DUal-Zone ConDenSer SeqUenCe oF operation

EMI America Series condensers are

designed to operate with EMI America

Series evaporators. Both the condenser

(outdoor unit) and evaporator (indoor

unit) have a high volt service connection.

Each is to be independently connected to

the electrical service panel. (See the unit

name plate for the correct breaker type
and size). The outdoor and indoor units

are also connected to each other through

a low volt interconnect wiring. A 24v trans-

former located in the indoor unit provides
the low v

olt power source.

Straight cool condensers are designed

to operate as a single stage cooling unit.

Heat pump condensers are designed to

operate as a single stage cooling two

stage heating unit. For proper operation

the unit must be matched with an appro-

priate EMI indoor unit with unit mounted
controls and/or wall mounted thermostat.

For two-stage heating operation the in-

door unit must be equipped with an elec-

tric strip heater.