EMI Volts/HZ/pH User Manual

Page 7

Advertising
background image

www.enviromaster.com

Side Discharge Condensers

7

inStallation inStrUCtionS

10. T

o replace side panel slide the slotted

holes of the panel onto the loosened

screws of the front panel so that the

edge of the front panel covers the edge

of the side panel.

eleCtriCal Wiring

Continued

11. Fasten all remaining loose screws.

reFrigerant piping

The system will support refriger-

ant runs to the inside unit of up to 100'

equivalent feet with a 35' rise included.

The units are furnished with sweat con-

nections and are equipped with refrigerant

valves and Schrader fittings for charging

and taking pressure readings. The follow-

ing precautions should be made:

• Be certain no burrs remain on the

fittings.

• Use only clean refrigeration tubing.
• Use tube benders to guard against

kinking.

• Avoid piping on wet and rainy days

and insulate suction line. Be certain

that plastic end caps remain in place

when inserting through wall openings.

Isolate tubing from transmitting vibra-

tion to the building or unit and avoid

contact with sharp edges. refrigera-
tion valves should be wrapped with
a wet rag "heat sink" to protect
valves while brazing.

note:

It is recommended that a

filter drier be installed in liquid line, at

the indoor unit on models that a filter

drier is not already factory installed

(i.e. 18K and larger).

interConneCting tUbing

SpeCiFiCationS

S1

model

maX.

length

max.

lift

liquid

line o.D.

Suction

line o.D.

09

100’

35’

1/4"

1/2"

12

100’

35’

1/4"

1/2"

18

100’

35’

3/8"

5/8"

24

100’

35’

3/8"

3/4"

30

100’

35’

3/8"

3/4"

36

100’

35’

3/8"

3/4"

S2C tUbing SpeCiFiCationS

Circuit

Size

line Sizes o.D.

liquid

Suction

09, 12

1/4”

1/2”