Side Discharge Condensers

8

Figure 1

Condenser

Evaporator

30'

15'

p-trap inStallation

• A P-trap is recommended when the suc-

tion riser is equal to or greater than 20

feet in height.

• When the condenser is installed above

the evaporator, the P-trap will help the

return of oil back to the compressor.

• The placement of the P-trap should be

at the halfway mark of the suction riser.

For example if the suction riser is 30 feet

tall then a P-trap is recommended at the

15 foot mark of the suction riser (see

Figure 1).

• A P-trap may be fabricated using (2) street

elbows and (2) regular elbow. A prefab-

inStallation inStrUCtionS

ricated trap may be purchased from a

wholesaler or distributor however the trap

should be shallow as the (3) elbow con-

figuration. Each elbow is approximately

2 equivalent feet. One P-trap is equal to

approximately 12 equivalent feet.

note:

Avoid excessive oil buildup.

The P-trap should have a shallow depth

and a short horizontal section.

• P-traps are not required at the foot of the

hot gas risers due to increased oil flow at

higher temperatures.