www.enviromaster.com

Side Discharge Condensers

3

proDUCt DeSCription

The AmericaSeries S1C/H and S2C

condensing units are, air-cooled, vertically

arranged side discharge, high efficiency

units designed specifically to meet or ex-

ceed a 13 SEER rating.

The S1C 9,000-36,000 Btuh and S1H

9,000-24,000 Btuh capacity condensing unit

will provide cooling for a single evaporator,

as identified in the "S1C Specifications and

Dimensions" section on pages 23-24.

The S2C 18,000 (99) - 21,000 (92) and

23,000 (22) Btuh capacity condensing units

will provide cooling for two evaporators, as

identified on page 25 in the "S2C Specifica-

tions and Dimensions" section. The S1C/H

and S2C are quiet units that can be recom-

mended for both commercial and residential

applications.

Installation of the S1C/H and S2C

condensing units is simplified by a 24v

control interconnection from the evaporator

and multiple units can be lined up in close

proximity to an exterior wall. Service valves

are recessed to reduce tampering and

all 9,000-12,000 Btuh units are equipped

with a Duratec Performance Package that
includes an oversized suction accumula-

tor with surge baffles and enhanced oil

management, a factory installed solid core

filter drier and loss of charge switch. A field

installed crankcase heater is standard on

S1H 09 &12 (Thermostatically controlled)

models, and is available as optional equip-
ment on other models.

• Compressor and fan motor contactor

• Run capacitor

• Loss of charge switch (09 - 12 only)

• Low voltage terminal connections

• Large capacity suction accumulator

(09 - 12 only)

• Solid core filter drier (09 - 12 only)

• Thermostatically controlled crankcase

heater (09 - 12 S1H’s)

• H.P.S. (High pressure switch)

- Standard on S1H’s (heat pumps)

- Standard on S1C’s 18K and above.

• Low Ambient controls

for operation

down to 32º F standard, factory in-
stalled

on all S1H’s (heat pumps)

• Field installed crankcase heater

for straight cool units (standard on

9,000-12,000 Btuh S1H’s Thermostati-

cally controlled)

• Straight cool hard start (standard on

all S1H’s)

• 115v (9,000-12,000 Btuh only)

• Copper/copper coils (sea coast use)

• Low Ambient controls

for operation down

to 32º F, specify this option for S1C or

S2C systems (standard on S1H’s) that

will be operated in cooling mode at

outside temperatures below 60º F

(field

installed kit)

• Low Ambient for operation down to 0º F

for S1C, S1H or S2C systems (consult

factory for availability)

inStaller SUpplieD itemS

• Power wiring

• Low volt wiring (18 awg minimum)

• Secure mounting pad or foundation

• Refrigerant piping (if not purchased

from EMI)

• High Volt Disconnect

• Refrigerant for charging interconnect

piping (see charge table on page 10)

itemS For ConSiDeration

low ambient controls are required when

the system is asked to cool at outdoor tem-

peratures below 60º F, this may cause dam-

age to the compressor and coil, and may

Thermostatically controlled crankcase
heater

– This feature energizes the crank-

case heater only when needed, removes

the heater from the electrical circuit at

conditions where it’s not required, saving

unnecessary Watts, and increasing overall

system efficiency.

ControlS anD ComponentS

(Factory Installed or Supplied)

SYStem optionS

Advertising