Installation instructions (continued) – Empire Products DVC-35T-1 User Manual

Page 11

Advertising
background image

13119-6-0107

Page 11

Installing a Vent Near a Window Ledge,

Other Type of Projection or on Siding (vinyl, aluminum, etc.)

Direct vent furnaces are designed to be installed on a uniform

outside wall. When the wind comes from any angle (up, down or

from either side), it must hit the vent cap equally over both the air

inlet and the flue outlet portions of the vent. Any wall projection,

such as a door or window casing, which disturbs the wind on one

side of the air inlet section will result in back pressure on the flue

section smothering the flame and eventual pilot outage.
When the vent cap is to be installed on siding or it appears that a

projection within 6” of any side of the air inlet section could shield

the air inlet section, the entire vent should be supported away from

the wall at least the distance of the projection. 2” x 4” framing

whose outside dimensions match the overall dimensions of the

mounting plate is recommended. The 2” x 4” framing protects

siding from possible warpage or discoloration. All joints can then

be sealed and painted. The wall depth plus the additional depth

of the 2” x 4” framing should not exceed a total depth of 14” for

DVC-35T. (See Figure 10)
Vinyl siding vent kit, DV-822, is available from Empire Comfort

Systems, Inc. The depth is 3”, which enables the vent cap to be

extended away from siding or projections. The wall depth plus the

additional 3” depth of the vinyl siding vent cap extension should

not exceed a total depth of 19” for DVC-35T. (See Figure 11)

Warning: When vinyl siding vent kit, DV-822 or 2” x 4”

framing is added to an existing installation (furnace is

installed) do not attempt to add sections of pipe to the flue

outlet tube or air inlet tube. An air tight seal is required for

both tubes. Refer to Parts List, page 16 to order tubes.

Figure 10

Figure 11

Installing Vent Assembly

Attention: DO NOT attempt to cut vent tubes. When you order

appropriate vent kit for measured wall depth the vent tubes will

fit together.

1. Place provided caulking beneath the collar of the outside

mounting plate. Use additional caulking to correct uneven wall

surface, such as clapboard.

2. Insert six inch air tube on outside mounting plate INTO six

inch air tube attached to air drop. Place four inch flue tube

on vent cap OVER four inch flue tube attached to outlet box.

Position the outside mounting plate so that six inch air tube

has a slight downward slope to the outside. The downward

slope is necessary to prevent the entry of rainwater. Attach

outside mounting plate to exterior wall with four (4) 10 x 1 1/2”

screws.

3. Installation is completed.
Reassembly And Resealing Vent-Air Intake System

When vent-air intake system is removed for servicing the furnace,

the following steps will assure proper reassembly and resealing of

the vent-air intake assembly.

1. Remove old caulking beneath the collar of the outside mounting

plate. Apply new caulking beneath the collar of the outside

mounting plate. Use additional caulking to correct uneven wall

surface, such as clapboard.

2. Insert six inch air tube on outside mounting plate INTO six

inch air tube attached to air drop. Position the outside mounting

plate so that six inch air tube has a slight downward slope to

the outside. The downward slope is necessary to prevent the

entry of rainwater. Attach outside mounting plate to exterior

wall with four (4) 10 x 1 1/2” screws.

3. Place four inch flue tube on vent cap OVER four inch flue tube

attached to outlet box. Attach vent cap to outside mounting plate

with three (3) 10 x 1/2” screws.

4. Reassembly and resealing vent-air intake system is

completed.