Dvc-35ipt intermittent pilot sequence of operation – Empire Products DVC-35T-1 User Manual

Page 18

Advertising
background image

Page 18

13119-6-0107

START

SYSTEM CHECK

TRIAL FOR

IGNITION

MAIN BURNER

OPERATION

END

(1) Ignitor will turn OFF about 30 seconds into the trial for ignition if the pilot flame has not lit. It will turn back ON for the final 30 seconds

of the 90 second trial for ignition. The pilot valve will be energized during the entire trial for ignition. This is normal operation for this gas

ignition system.

Apply 24 VAC

to Appliance

Thermostat

Calls for Heat

Flame Signal

Detected

Internal Check

OK

Pilot Light and lame is

Sensed During Trial

For Ignition (1)

Ignitor Off

Main Valve Opens

Pilot Valve Opens

Ignitor Powered

Flame Signal

Lost?

Thermostat Call

for Heat Ends

Main Pilot Valve

Close

Flame Lost More

Than 5 Times in

One Call for Heat

Main Pilot

Valves Close

3 Second Flame

Failure Recycle

Delay

Pilot Valve Closes

Ignition OFF

5 Minute Retry

Delay

Pilot Valve Ignition OFF

Wait for Flame Signal to

Disappear

DVC-35IPT INTERMITTENT PILOT SEQUENCE OF OPERATION