Ip system troubleshooting sequence – Empire Products DVC-35T-1 User Manual

Page 19

Advertising
background image

13119-6-0107

Page 19

aa

SmartValve™ System Troubleshooting Sequence

Note: Before Troubleshooting, Become Familiar

with the Sequence of Operation

IP SYSTEM TROUBLESHOOTING SEQUENCE

NO

NO

NO

YES

YES

NO

• Turn OFF Gas Supply

• Disconnect System Control

Harness

• Set Thermostat to Call for

Heat

Plug Harness into SmartValve

Control

Wait for Internal Check Delay

(SV9501)

Igniter Warms UP and

Glows Red

System is Okay

Main Valve Opens and

Main Burner Lights

• Turn On Gas Supply

• Pilot Burner Lights

Check for Proper Voltage at

Control Harness (See Inset A

-Voltage Should be 24V

Between Thermostat and

24V Common, and 24V

Between 24V Common and

24V Hot.)

Reconnect Pilot Burner Cable

• Check that Pilot Gas is Flowing

Wait to Assure Pilot Gas Tubing

is Purged.

Replace Igniter/Flame Rod Assembly

Note: Igniter Will Cycle OFF

and Back ON Once During

the 90 Second Ignition Trial

Cycle Thermostat OFF and Back ON

Main Burner Lights

Replace SmartValve Control

Check Transformer and Line

Volt Supply

• Check that Pilot Flame Makes Good

Contact with Pilot Burner Flame

Rod

• Check for Good Electrical

Connection Through the Pilot

Tubing

• If Both of the Above are Good,

Replace Igniter/Flame Rod

• Measure Voltage Between 24V Hot

and 24V Common Leads to

SmartValve Control. Must Measure

at Least 19.5 VAC with Igniter

Powered. See Inset A to Identify

Proper Lead. This Check Must be

Done with the SmartValve Control

Connected and Igniter Powered.

Unplug Pilot Burner Cable.

Measure Voltage at SmartValue

HSI Element Output (See Inset B)

24V Nominal

YES

NO

NO

NO

NO

YES

YES

YES

YES

CHECK

• Line Voltage Power

• Low Voltage Transformer

• Limit Controller

• Thermostat

• Wiring

Replace SmartValve Control

Replace SmartValve Control

START

Replace Igniter/Flame Rod Assembly

Reconnect Pilot Burner Cable

INSET A

24Volt

Thermostat

24

Volts

24 Volt

Common

24

Volts

24 Volt

Hot

EFT

Output

End View

of Control

Harness

Connector

INSET B

HSI

Terminals

DVC-35IPT INTERMITTENT PILOT SYSTEM TROUBLESHOOTING SEQUENCE