Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 76

Advertising
background image

76

U

SE

FUNCTION

DESCRIPTION

PREDEFINED

POSSIBLE CONFIGURATIONS

MODE

Alarm threshold

for maximum

load

Selects the user

overload limit

Disabled

Disabled
0 ÷ 103 in 1% steps

Display

brightness

Selects the level of

brightness of the LCD

display

Maximum

Minimum ÷ Maximum in 20 steps

Acoustic alarm

Selects the operating
mode of the acoustic

alarm

Low

Normal
Low: does not sound for momentary

bypass intervention

Auxiliary socket

(power share)

Selects the operating

mode of the auxiliary

socket

Always

connected

Always connected
Disconnection after n seconds of

operation from battery

Disconnection after n seconds from

the end of discharge prealarm signal

... (see the configuration software

manual)

ADVANCED SETTINGS

Input frequency

tolerance

Selects the allowed

input frequency range

for the passage onto

bypass and for

synchronization of the

output

± 5%

± 0.25%
± 0.5%
± 0.75%
± 1 ÷ ±10 in 1% steps

Bypass voltage

thresholds

Selects the allowed

voltage range for the

passage onto bypass

Low: 180V
High: 264V

Low: 180 ÷ 200 in 1V steps

High: 250 ÷ 264 in 1V steps

Bypass voltage

thresholds for

ECO

Selects the allowed

voltage range for

operation in ECO

mode

Low: 200V
High: 253V

Low: 180 ÷ 220 in 1V steps

High: 240 ÷ 264 in 1V steps

Sensitivity of

intervention for

ECO

Selects the sensitivity

of intervention during

operation in ECO

mode

Normal

Low
Normal
High

Power supply of

the load in stand-

by

Power supply of the

load on bypass with

UPS switched off

(stand-by state)

Disabled (load

NOT powered)

Disabled (not powered)
Enabled (powered)

Bypass operation

Selects the mode of

use of the bypass line

Enabled /

High sensitivity

Enabled/High sensitivity
Enabled/Low sensitivity
Disabled with input/output

synchronization

Disabled without input/output

synchronization