Alarm codes, Troubleshooting – Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 81

Advertising
background image

81

TROUBLESHOOTING

ALARM CODES

Using a sophisticated self check system, the UPS can verify and indicate on the display panel any faults
and/or malfunctions that may occur during the normal operation of the device. In the event of a problem, the
UPS indicates this by displaying the code and the type of alarm (FAULT and/or LOCK).

FAULT

FAULT signals can be subdivided into three categories.

Faults: these are “minor” problems that do not stop the UPS but reduce performance or prevent the

use of some of its functions.

CODE

DESCRIPTION

A06

Sensor1 temperature less than 0°C

A08

Sensor2 temperature less than 0°C

A11

Input relay locked (does not open)

A54

Load > preset user threshhold

A61

Batteries to be replaced

A62

No Battery box or not connected

A63

Waiting to recharge batteries


Alarms: these are more critical problems than faults since if they persist, even for a very short time,

they may cause the UPS to stop.

CODE

DESCRIPTION

F03

Auxiliary power supply not correct

F04

Dissipators overtemperature

F05

Temperature sensor1 faulty

F07

Temperature sensor2 faulty

F10

Input fuse broken or input relay locked (does not close)

F13

Condenser precharge failed

F21

Condenser bank overvoltage

F40

Inverter overvoltage

F41

Direct voltage in output

F42

Inverter voltage not correct

F43

Inverter undervoltage

F50

Overload: load > 103%

F51

Overload: load > 125%

F52

Overload: load > 150%

F53

Short circuit

F55

Waiting for reduction of load to return onto inverter

F60

Batteries overvoltage