Attery, Ox technical data table, Able of overload times – Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 85: Echnical data table

Advertising
background image

85

T

ECHNICAL DATA TABLE

B

ATTERY

B

OX TECHNICAL DATA TABLE

BASIC MODELS

BBX SDL 240V BB NP A3

BBX SDL 240V BB NP A5

BATTERY

Nominal voltage

[Vdc]

240

End of charge voltage

[Vdc]

273

No. of batteries/V

20 / 12

SUNDRY

Ambient temperature (1)

[°C]

0 – 40

Humidity

< 90% non condensing

Protections

overcurrent - short circuit

Dimensions H x L x D

[mm]

455 x 175 x 660

Weight

[Kg]

63

65

(1) 20-25°C for extended battery life


T

ABLE OF OVERLOAD TIMES

OVERLOAD TIMES

OPERATION FROM

BYPASS

INVERTER

100% < Load 125%

Bypass active after 2 sec

Locked after 120 sec

Locked after 60 sec

125% < Load 150%

Bypass active after 2 sec

Locked after 4 sec

Locked after 4 sec

Load > 150%

Bypass active instantly

Locked after 1 sec

Locked after 0.5 sec




Advertising