All installations and services must be performed by qualified service personnel.

9

The horizontal furnace installation should be on a service platform large enough to allow for proper
clearances on all sides and service access to the front of the furnace (See Table 1). If the furnace is
suspended, it must be supported at both ends and in the middle with clearance allowed for removal of
both access doors. Gas supply line contact is only permissible between lines

formed by the intersection of

the top and two sides of the furnaces casing and the building joists, studs, or framing (See Figure 1).

Equipment must be installed in accordance with regulations of the National Board of Fire
Underwriters and the National Fuel Gas Code. Authorities having jurisdiction should be consulted
before installations are made.


C. Replacing An Existing Furnace From A Common Vent

: These furnaces may NOT be common vented with any other appliance.


D. General Requirements For Venting Models CHX3 / CDX3

The CHX3 / CDX3 furnace venting system must be installed by a qualified service person in
accordance with local installation codes and these instructions. In the absence of applicable local
codes, conform to the National Fuel Gas Code, NFPA 54 /ANSI Z223.1-2002, or latest edition thereof.

Installation shall, at least, conform to the following requirements.

1. The exhaust vent / combustion air intake terminations specified by Thermo Products, in this

manual, shall be used.

2. All plastic pipe and pipe fittings sourced to complete the exhaust vent and air intake

systems shall be constructed of rigid PVC (polyvinyl chloride) thermoplastic. All
components shall have a wall thickness equivalent to Schedule 40 series materials.

In addition, all sourced PVC components shall be listed by a nationally recognized testing agency
(e.g. NSF, UL, etc.) as conforming to one (1) or more of the following design standards.

PVC Pipe Designation

Design Standard

Cellular Core

ASTM-F891

DWV (Drain-Waste-Vent) ASTM-D2665

Schedule 40

ASTM-D1785

3. The exhaust vent pipe and combustion air pipe shall be at least as large as the exhaust vent / air

intake pipe specified by Thermo Products. Size reduction is never permissible. The required
exhaust vent / air intake pipe sizes are:

nominal 2-inch diameter IPS, Schedule 40 series, PVC thermoplastic pipe, for models
CHX3-75 & CDX3-75
, or

nominal 3-inch diameter IPS, Schedule 40 series, PVC thermoplastic pipe, for models
CHX3-100 / -125 & CDX3-100 / -125
.

4. The furnace model series CHX3 / CDX3 shall not be common vented with any other appliance,

including those burning solid fuels.

5. All horizontal runs of exhaust vent pipe shall slope upward at least ¼ inch per foot from the outlet

of the furnace (for model CHX3), or the outlet of the drain tee (for the model CDX3), to the vent
termination, beyond the outside wall. This slope will permit proper drainage of the condensate.