All installations and services must be performed by qualified service personnel.

49

SET THERMOSTAT TO CALL FOR HEAT

(MAKE CERTAIN ROOM TEMPERATURE IS BELOW THERMOSTAT SETTING)

CHECK INPUT POWER,

DOOR INTERLOCK,

SERVICE SWITCH

AND FUSES

IS THE INDUCER

BLOWER OPERATING?

CHECK 115 VOLT

CONNECTIONS. IF OK,

REPLACE TRANSFORMER

YES

NO

YES

YES

NO

NO

IS THERE 24V

ACROSS R AND B/C

NO

IS THERE 24 VOLTS

ACROSS "R" AND "W1"?

CHECK WIRING TO

THERMOSTAT. IF OK,

REPLACE THERMOSTAT.

YES

NO

CHECK WIRING TO INDUCER

AND IF OK, REPLACE

INDUCER ASSEMBLY.

YES

YES

NO

TROUBLESHOOTING GUIDE

THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO CALL FOR

HEAT. THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF

MALFUNCTION OR DEVIATION FROM THE NORMAL OPERATION.

NOTE: REFER TO PAGE 48 FOR DEFINITION OF DIAGNOSTIC LEDS.

TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.

IS THERE 120 VOLTS

ACROSS "L1" AND

"NEUTRAL" AT THE

50V51-843 CONTROL

MODULE?

IS THERE 24 VOLTS

ACROSS "TH" & "TR"

AT THE INTEGRATED

CONTROL MODEL

50V51-843?

CHECK FUSE ON

W/R 50V51-843

IS THERE LINE VOLTAGE

ACROSS INDUCER POWER

TERMINALS "IND HI" TO

"IND N" OR "IND LO" TO

"IND N" AT THE 50V51-843

CONTROL?

REPLACE THE

50V51-843 CONTROL.