Thermo Pride Spirit Gas TG9S Single Stage PSC 95.5% User Manual

Page 28

Advertising
background image

1083287-UIM-A-0114

28

Johnson Controls Unitary Products

Ambient Combustion Air Supply

This type installation will draw the air required for combustion from
within the space surrounding the appliance and from areas or rooms
adjacent to the space surrounding the appliance. This may be from
within the space in a non-confined location or it may be brought into the
furnace area from outdoors through permanent openings or ducts. It is
not piped directly into the furnace. A single, properly sized pipe from the
furnace vent connector to the outdoors must be provided. It is recom-
mended that the supplied intake coupling & 18” of pipe be attached to
the furnace to prevent accidental blockage of the combustion air intake.

An unconfined space is not less than 50 cu.ft (1.42 m

3

) per 1,000 Btu/

hr (0.293 kW/h) input rating for all of the appliances installed in that
area.

Rooms communicating directly with the space containing the appli-
ances are considered part of the unconfined space, if doors are fur-
nished with openings or louvers.

A confined space is an area with less than 50 cu.ft (1.42 m

3

) per 1,000

Btu/hr (0.293 kW/h) input rating for all of the appliances installed in that
area. The following must be considered to obtain proper air for combus-
tion and ventilation in confined spaces.

Dampers, Louvers and Grilles

The blocking effects of louvers, grilles and screens must be given con-
sideration in calculating free area. If the free area of a specific louver or
grille is not known, refer to Table12 to estimate free area.

* Do not use less than 1/4” (6.4 mm) mesh
+ Free area of louvers and grille varies widely; the installer should follow

louver or grille manufacturer’s instructions.

1.

The free area of a supply air opening shall be calculated by sub-
tracting the blockage area of all fixed louvers grilles or screens from
the gross area of the opening.

2.

Apertures in a fixed louver, a grille, or screen shall have no dimen-
sion smaller than 1/4” (6.4 mm).

3.

A manually operated damper or manually adjustable louvers are
not permitted for use.

4.

A automatically operated damper or automatically adjustable lou-
vers shall be interlocked so that the main burner cannot operate
unless either the damper or the louver is in the fully open position.

FIGURE 37: Combustion Airflow Path Through The Furnace Casing

This type of installation requires that the supply air to the appliance(s)
be of a sufficient amount to support all of the appliance(s) in the area.
Operation of a mechanical exhaust, such as an exhaust fan, kitchen
ventilation system, clothes dryer or fireplace may create conditions
requiring special attention to avoid unsatisfactory operation of gas
appliances. A venting problem or a lack of supply air will result in a
hazardous condition, which can cause the appliance to soot and gen-
erate dangerous levels of CARBON MONOXIDE, which can lead to
serious injury, property damage and / or death.

COMBUSTION AIR

Vent pipe clamps
into outlet of
drain coupling

Table 12: Estimated Free Area

Wood or Metal

Louvers or Grilles

Wood 20-25%*

Metal 60-70% *

Screens+

1/4” (6.4 mm)

mesh or larger 100%

When a Category I furnace is removed or replaced, the original vent-
ing system may no longer be correctly sized to properly vent the
attached appliances.

An improperly sized vent system can cause CARBON MONOXIDE to
spill into the living space causing personal injury, and or death.

Table 13: Unconfined Space Minimum Area

BTUH Input Rating

Minimum Free Area

Required for Each Opening

40,000

40 in

2

(258 cm

2

)

60,000

60 in

2

(387 cm

2

)

80,000

80 in

2

(516 cm

2

)

100,000

100 in

2

(645 cm

2

)

120,000

120 in

2

(742 cm

2

)

130,000

130 in

2

(838 cm

2

)

Table 14: Free Area

BTUH Input

Rating

Minimum Free Area Required for Each Opening

Horizontal Duct

(2,000 BTUH)

Vertical Duct or

Opening to Outside

(4,000 BTUH)

Round Duct

(4,000 BTUH)

40,000

20 in

2

(129 cm

2

)

10 in

2

(64 cm

2

)

4” (10 cm)

60,000

30 in

2

(193 cm

2

)

15 in

2

(97 cm

2

)

5” (13 cm)

80,000

40 in

2

(258 cm

2

)

20 in

2

(129 cm

2

)

5” (13 cm)

100,000

50 in

2

(322 cm

2

)

25 in

2

(161 cm

2

)

6” (15 cm)

120,000

60 in

2

(387 cm

2

)

30 in

2

(193 cm

2

)

7” (18 cm)

130,000

65 in

2

(419 cm

2

)

33 in

2

(213 cm

2

)

7” (18 cm)

EXAMPLE: Determining Free Area.
Appliance

1 Appliance

2 Total Input

100,000

+ 30,000 = (130,000

 4,000) = 32.5 Sq. In. Vertical

Appliance

1 Appliance

2 Total Input

100,000

+ 30,000 = (130,000

 2,000) = 65 Sq. In. Horizontal

Advertising