Notice – Thermo Pride Spirit Gas TG9S Single Stage PSC 95.5% User Manual

Page 9

Advertising
background image

1083287-UIM-A-0114

Johnson Controls Unitary Products

9

SECTION III: FILTERS

FILTER INSTALLATION

All applications require the use of a field installed filter. All filters and
mounting provision must be field supplied.

Filters must be installed external to the furnace cabinet. DO NOT
attempt to install filters inside the furnace.

1. Air velocity through throwaway type filters may not exceed 300 feet per min-

ute (91.4 m/min). All velocities over this require the use of high velocity fil-
ters.

2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For

CFM greater than 1800, you may use two side returns or one side and the
bottom or one side return with a transition to allow use of a 20x25 filter.

FIGURE 13: Dimensions

FRONT

33

A

LEFT SIDE

Combustion Air Inlet

Condensate Drain
(Downflow)

Vent Outlet

Thermostat
Wiring

28.5”

Gas Pipe
Entry

Electrical
Entry

Condensate
Drain

Thermostat
Wiring

RIGHT SIDE

Vent Outlet

Condensate Drain
(Downflow)

14”

1”

1.5”

23”

Combustion Air Inlet

Gas Pipe
Entry

Electrical
Entry

Condensate
Drain

Optional Return Air
Cutout (Either side)

29.5”

(For Cladded door add appoximately an additional .75”)

C

SUPPLY END

.56”

.56”

20”

B

3”

23.8”

.56”

Combustion
Air Inlet

Vent
Outlet

RETURN END

B

24.25”

Table 3: Cabinet and Duct Dimensions

BTUH (kW)

Input

Nominal

CFM (m

3

/min)

Cabinet

Size

Cabinet Dimensions (Illustrated in Figure 13)

Approximate

Operating Weights

A (in)

A (cm)

B (in)

B (cm)

C (in)

C (cm)

Lbs (kg)

40 (11.7)

800 (22.7)

A

14 1/2

36.8

13 3/8

34.0

11 3/4

29.8

113 (51.3)

60 (17.6)

1000 (28.3)

A

14 1/2

36.8

13 3/8

34.0

11 3/4

29.8

118 (53.5)

60 (17.6)

1200 (34.0)

B

17 1/2

44.4

16 3/8

41.6

13 1/4

33.7

122 (55.3)

80 (23.4)

1200 (34.0)

B

17 1/2

44.4

16 3/8

41.6

14 3/4

37.5

126 (57.2)

80 (23.4)

1600 (45.3)

C

21

53.3

19 7/8

50.5

16 1/2

41.9

136 (61.7)

80 (23.4)

2200 (62.3)

C

21

53.3

19 7/8

50.5

16 1/2

41.9

139 (63.0)

100 (29.3)

1600 (45.3)

C

21

53.3

19 7/8

50.5

18 1/4

46.4

142 (64.4)

100 (29.3)

2000 (56.6)

C

21

53.3

19 7/8

50.5

18 1/4

46.4

145 (65.8)

120 (35.1)

1600 (45.3)

D

24 1/2

62.2

23 3/8

59.4

21 3/4

55.2

153 (69.4)

120 (35.1)

2000 (56.6)

D

24 1/2

62.2

23 3/8

59.4

21 3/4

55.2

156 (70.7)

130 (38.1)

2000 (56.6)

D

24 1/2

62.2

23 3/8

59.4

No Hole

No Hole

160 (72.5)

Single side return above 1800 CFM is approved as long as the filter
velocity does not exceed filter manufacturer’s recommendation and a
transition is used to allow use on a 20x25 filter.

NOTICE

Table 4: Recommended Filter Sizes (High Velocity 600 FPM)

CFM (m³/min)

Cabinet Size

Side (in)

Bottom (in)

800 (22.7)

A

16 x 25

14 x 25

1000 (28.3)

A

16 x 25

14 x 25

1200 (34.0)

A

16 x 25

14 x 25

1200 (34.0)

B

16 x 25

16 x 25

1600 (45.3)

B

16 x 25

16 x 25

1600 (45.3)

C

16 x 25

20 x 25

2000 (56.6)

C

(2) 16 x 25

20 x 25

2200 (62.3)

C

(2) 16 x 25

20 x 25

2000 (56.6)

D

(2) 16 x 25

22 x 25