Elektra Beckum Cool 401 User Manual

Page 22

Advertising
background image

22

11.02

Part 5

Maintenance

5.2

Trouble shooting

Fig. 19: Failure indication

general

5.2.1

electronic regulator
failure indication

Fig. 20: electronic regulator

Failure indication

Cause

5.2.1.1 F1 sensor pressure

dewpoint defective

5.2.1.2 F2 sensor ambient

temperature defective

5.2.1.3 EH EEPROM:

electronic regulator

5.2.1.4 EL electronic regulator

defective

5.2.1.5 FH refrigerant-

overpressure

5.2.1.6 EU low voltage

5.2.1.7 H1 dew point too high

5.2.1.8 L1 dew point too low

Remedy

Check sensor connection, replace sensor

Replace regulator

Restart CA-dryer, if not possible:
Replace regulator

Restart CA-dryer, if not possible:
Replace regulator

See 5.2.5

Ensure electric power supply acc. to technical data.

See 5.2.4

See 5.2.6.3

CA-dryer stopped

Display changes be-
tween set value and
failure indication
(refrigerant overpres-
sure)

Failure indication: CA-dryer
stopped.