9

Power Measurement

Polarity configuration note:

when measuring load circuits with power absorptions, positive (‘+’ implied) w or kw (Real
Power) readings indicate correct measurement setups. negative readings (“-“ segment on)
indicate either the clamp-on jaws direction or the test leads polarity is reversed in such
cases. Correct the setups to get correct readings.

Power Measurement - Single Phase (Ø) (see figure 8)

Select the Power position.
Press SELECt button momentarily to select W (real power), VAR (reactive power) or VA
(apparent power) measurement functions.
Connect CoM input to neutral or gRD.
Connect ‘ + ‘ input to the phase being tested.
Clamp jaws around the phase wire
The display will show reading, W (real power), VAR (reactive power) or VA (apparent
power) measurement and Pf.

Power Measurement – 3 Phase (Ø) - 3 Wire (see figure 9)

Select the Power position.
Press SELECt button momentarily to select W (real power) or VA (apparent power)
measurement functions.
Connect CoM input to Ø 3 terminal .
Connect ‘ + ‘ input to Ø 1 terminal
Clamp jaws around to Ø 1 wire
The display will show reading, W (real power) or VA (apparent power) measurement
and Pf.
write down the reading as kw1, kVA1
Connect CoM input to Ø 3 terminal .
Connect ‘ + ‘ input to Ø 2 terminal
Clamp jaws around to Ø 2 wire
The display will show reading, W (real power) or VA (apparent power) measurement
and Pf.
write down the reading as kw2

Load

balanced

Unbalanced

kw Total

kw1 + kw2

kw1 + kw2

kVA Total

1.732 * kVA1

not applicable

kVAR Total

√ kVA Total

2

- kw Total

2

not applicable

Power Measurement - 3 Phase (Ø) - 4 Wire (see figure 10)

Select the Power position.
Press SELECt button momentarily to select W (real power), VA (apparent power) or
VAR (reactive power) measurement functions.

1.
2.

3.
4.
5.
6.

1.
2.

3.
4.
5.
6.

7.
8.
9.
10.
11.

12.

1.
2.