Amprobe ACD-30P Clamp-On-Power-Meters User Manual

Page 15

Advertising
background image

14

Range:

0.0% to 999.9%

2)

Harmonic

Accuracy

3)

fundamental

± (1.5% rdg + 6d)

2nd ~ 3rd

± (5.0% rdg + 6d)

4th ~ 16th

± (2.5% rdg + 6d)

17th ~ 46th

± (3.0% rdg + 6d)

47th ~ 51st

± (4.5% rdg + 6d)

1)

ThD-f is defined as: (Total harmonic RMS / fundamental RMS) x 100%

2)

Range for Dual Display mode: 0% to 99%

3)

Specified accuracy @ ACA fundamental > 5A ; ACV fundamental > 50V

total Power factor (Pf)

Range

Accuracy

1)

0.10 to 0.99

f to 21st harmonic

22nd to 51st harmonic

± 3d

± 5d

1)

Specified accuracy @ ACA fundamental > 2A ; ACV fundamental > 50V

Power (VA)

Range

Accuracy

1) 2)

0 to 600.0 kVA

f to 10th

11th to 46th

47th to 51st

@ Pf = 0.99 to 0.1

± (2.0% rdg + 6d)

± (3.5% rdg + 6d)

± (5.5% rdg + 6d)

Power (kW and kVAR)

Range

Accuracy

1) 3)

0 to 600.0 kw
/ kVAR

f to 10th

11th to 25th

26th to 46th

47th to 51st

@ Pf = 0.99 to
0.70

± (2.0% rdg + 6d

± (3.5% rdg
+ 6d)

± (4.5% rdg
+ 6d)

± (10% rdg +6d)

@ Pf = 0.70 to
0.50

± (3.0% rdg + 6d)

@ Pf = 0.50 to
0.30

± (4.5% rdg + 6d)

@ Pf = 0.30 to
0.20

± (10% rdg + 6d)

± (15% rdg +6d)

1)

Specified accuracy is for ACA clamp measurement at the center of jaws. when the

conductor is not positioned at the jaw center, position errors introduced are: Add 1%
rdg to specified accuracy for ACA measurements made wiThin jaw marking lines (away