Amprobe ACD-30P Clamp-On-Power-Meters User Manual

Page 11

Advertising
background image

10

Connect CoM input to neutral or ground terminal.
Connect ‘ + ‘ input to Ø 1 terminal
Clamp jaws around to Ø 1 wire
The display will show reading, W (real power), VA (apparent power)or VAR (reactive
power) measurement and Pf.
write down the reading as kw1, kVA1, kVAR1
Connect CoM input to neutral or ground terminal.
Connect ‘ + ‘ input to Ø 2 terminal
Clamp jaws around to Ø 2 wire
The display will show reading, W (real power), VA (apparent power) or VAR (reactive
power) measurement and Pf.
write down the reading as kw2, kVA2, kVAR2
Connect CoM input to neutral or ground terminal.
Connect ‘ + ‘ input to Ø 3 terminal
Clamp jaws around to Ø 3 wire
The display will show reading, W (real power), VAR (reactive power) or VA (apparent
power) measurement and Pf.
write down the reading as kw3, kVA3, kVAR3

Load

balanced

Unbalanced

kw Total

3 * kw1

kw1 + kw2 + kw3

kVA Total

3 * kVA1

kVA1 + kVA2 + kVA3

kVAR Total

3 * kVAR1

kVAR1 + kVAR2 + kVAR3

Power factor (Pf)
Total Power factor = Real Power (V rms * A rms * Cos θ )/Apparent Power (V rms * A rms)
A-lags” annunciator indicates an inductive circuit, or Current A lags Voltage V (phase-
shift angle θ is “+”).
A-lags” not visible indicates a capacitive circuit, or Current A leads Voltage V (phase-shift
angle θ is “-”).

MAINtENANCE AND REPAIR
if there appears to be a malfunction during the operation of the meter, the following
steps should be performed in order to isolate the cause of the problem:

Check the battery.
Review the operating instructions for possible mistakes in operating procedure.
inspect and test the test leads for a broken or intermittent connection.

except for the replacement of the battery or test probes, repair of the multimeter
should be performed only by a factory Authorized Service Center or by other qualified
instrument service personnel. The front panel and case can be cleaned with a mild solution
of detergent and water. Apply sparingly with a soft cloth and allow to dry completely
before using. Do not use aromatic hydrocarbons or chlorinated solvents for cleaning.