Plc5 processor – ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 111

Advertising
background image

DFNT ♦ ProLinx Gateway

Reference

EtherNet/IP Explicit Messaging Client/Server

Protocol Manual

ProSoft Technology, Inc.

Page 111 of 124

July 24, 2013

5.10 PLC5 Processor

The module can be used to receive messages from a PLC5 containing an
Ethernet interface. The module supports both read and write commands. A
discussion of each operation is provided in the following topics:

5.10.1 PLC5 Write Commands

Write commands transfer data from the PLC5 processor to the DFNT module. An
example rung used to execute a write command is shown in the following
diagram:

In order to complete the configuration of the MSG instruction, select the S

ETUP

S

CREEN

area of the MSG object. This displays the following dialog box.

Select the C

OMMUNICATION

C

OMMAND

to execute from the following list of

supported commands.
 PLC5 Type Write
 PLC2 Unprotected Write
 PLC5 Typed Write to PLC
 PLC Typed Logical Write
The T

ARGET

D

EVICE

D

ATA

T

ABLE

A

DDRESS

must be set to a valid file element

(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Write
message, set the address to the database index (such as, 1000) to consider with
the command.