Diagnostics and Troubleshooting

DFNT ♦ ProLinx Gateway

Protocol Manual

EtherNet/IP Explicit Messaging Client/Server

Page 56 of 124

ProSoft Technology, Inc.

July 24, 2013

4.2

Base Module LEDs

LED

State

Description

Power

Off

Power is not connected to the power terminals or source is insufficient
to properly power the module (minimum required is 800mA at 24 Vdc)

Green Solid

Power is connected to the power terminals.

Fault

Off

Normal operation.

Red Solid

A critical error has occurred. Program executable has failed or has
been user-terminated and is no longer running. Press Reset p/b or
cycle power to clear error. If not, use the Debug procedures described
later in this manual.

Cfg

Off

Normal operation.

Amber Solid

The unit is in configuration mode. The configuration file is currently
being downloaded or, after power-up, is being read, the unit is
implementing the configuration values, and initializing the hardware.
This will occur during power cycle, or after pressing the reset button. It
also occurs after a cold/warm boot command is received.

Err

Off

Normal operation.

Flashing

An error condition has been detected and is occurring on one of the
application ports. Check configuration and troubleshoot for
communication errors.

Solid Red

This error flag is cleared at the start of each command attempt
(Master/Client) or on each receipt of data (slave/adapter/server); so, if
this condition exists, it indicates a large number of errors are occurring
in the application (due to bad configuration) or on one or more ports
(network communication failures).

4.2.1 Ethernet LED Indicators

LED

State

Description

Data

OFF

No activity on the Ethernet port.

GREEN Flash

The Ethernet port is actively transmitting or receiving data.

Link

OFF

No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.

GREEN Solid

Physical network connection detected. This LED must be ON
solid for Ethernet communication to be possible.