ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 115

Advertising
background image

DFNT ♦ ProLinx Gateway

Reference

EtherNet/IP Explicit Messaging Client/Server

Protocol Manual

ProSoft Technology, Inc.

Page 115 of 124

July 24, 2013

The T

ARGET

D

EVICE

D

ATA

T

ABLE

A

DDRESS

must be set to a valid file element

(such as, N11:0) for SLC and PLC5 messages. The M

ULTI

H

OP

option must be

set to Y

ES

.

The M

ULTI

H

OP

tab portion of the dialog box must be completed as

displayed in the following window:

Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.

5.11.2 SLC5/05 Read Commands

Read commands transfer data to the SLC processor from the DFNT module. An
example rung used to execute a read command is shown in the following
diagram:

Advertising