4.5.2 Remote STS Error Codes

Code (Int)

Code (Hex) Description

0

0x0000

Success, no error

4096

0x1000

Illegal command or format

8192

0x2000

Host has a problem and will not communicate

12288

0x3000

Remote node host is missing, disconnected or shut down

16384

0x4000

Host could not complete function due to hardware fault

20480

0x5000

Addressing problem or memory protect rungs

24576

0x6000

Function not allowed due to command protection selection

26872

0x7000

Processor is in Program mode

-32768

0x8000

Compatibility mode file missing or communication zone problem

-28672

0x9000

Remote node cannot buffer command

-24576

0xA000

Wait ACK (1775-KA buffer full)

-20480

0xB000

Remote node problem due to download

-16384

0xC000

Wait ACK (1775-KA buffer full)

-12288

0xD000

Not used

-8192

0xE000

Not used

0xF0nn

Error code in the EXT STS byte (nn contains EXT error code)