Micrologix processor specifics – ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 88

Advertising
background image

Reference

DFNT ♦ ProLinx Gateway

Protocol Manual

EtherNet/IP Explicit Messaging Client/Server

Page 88 of 124

ProSoft Technology, Inc.

July 24, 2013

5.5

MicroLogix Processor Specifics

This section contains information specific to the MicroLogix processor based
family when used with the DF1 command set. The MicroLogix processor
commands support a file type field entered as a single character to denote the
data table to interface with in the command. This field is the same as that used
for a SLC processor. The following table defines the relationship of the file types
accepted by the module and the SLC file types:

5.5.1 SLC File Types

File Type

Description

S

Status

B

Bit

T

Timer

C

Counter

R

Control

N

Integer

F

Floating-point

Z

String

A

ASCII

The File Type Command Code is the ASCII character code value of the File Type
letter. This is the value to enter into the "File Type" parameter of the DF1
Command configurations in the data tables in the ladder logic.

Additionally, the SLC specific functions (502, 510 and 511) support a sub-
element field. This field selects a sub-element field in a complex data table. For
example, to obtain the current accumulated value for a counter or timer, the sub-
element field should be set to 2.

Advertising