6 float offset, 7 protocol, 8 baud rate – ProSoft Technology 5202-DFNT-MCM4 User Manual

Page 20

Advertising
background image

MCM ♦ ProLinx Gateway

MCM Protocol Configuration

Modbus Master/Slave

Driver Manual


Page 20 of 80

ProSoft Technology, Inc.

October 16, 2009

3.1.6 Float

Offset

0

TO

3998

This parameter defines the starting register for floating-point data in the internal
gateway database. This parameter is used only if the Float Flag is set to Y

ES

.

For example, if the Float Offset value is set to 3000 and the Float Start parameter
is set to 7000, the data returned as floating-point data for register 47001 (or
407001) will actually come from internal gateway registers 3000 and 3001. If the
requested address was 47002 (407002), the data will be returned from internal
registers 3002 and 3003. If the requested address was 47101 (407101), the data
will be returned from internal registers 3200 and 3201; and so on.

3.1.7 Protocol

RTU

ASCII

This parameter specifies the Modbus protocol version to be used on the port.
Valid Protocols are RTU and ASCII.

3.1.8 Baud

Rate

This is the baud rate to be used on the port. Enter the baud rate as a value.

Baud Rate

Parameter Value

110

110

150

150

300

300

600

600

1200

12

OR

1200

2400

24

OR

2400

4800

48

OR

4800

9600

96

OR

9600

14,400

14,

114

OR

14400

19,200

19,

192

OR

19200

28,800

28,

288

OR

28800

38,400

38,

384

OR

38400

57,600

57

OR

576

115,200

115

OR

1152

Note: On all ProLinx gateways, data from the application port on the main board, serial Port 0, is
not buffered. Packets go directly to and from the serial chipset to the processor. This has the
potential to cause the serial communications to become erratic at baud rates above 38,400 baud.

ProLinx gateways with 4 serial ports have a separate serial interface board for serial Ports 1, 2,
and 3. These serial ports are buffered, and can handle communications up to 115,200 baud.