MCM ♦ ProLinx Gateway

Modbus Port Expander (4102/5102-MBS3-MBM)

Modbus Master/Slave

Driver Manual


Page 48 of 80

ProSoft Technology, Inc.

October 16, 2009

7.1.1 Internal Slave ID

0

TO

255

This parameter defines the virtual Modbus slave address for all three slave ports
on the Port Expander. It should be set to the same value as the Slave ID of the
device attached to the gateway's Master port. Any commands received on the
slave ports, addressed to the node address entered here, will be passed by the
gateway to the slave attached to the gateway's Master port. Any response
received from the slave will be passed back through the gateway's slave port on
which it was received.

7.1.2 Protocol

RTU

ASCII

This parameter specifies the Modbus protocol version to be used on the port.
Valid Protocols are RTU and ASCII.

7.1.3 Baud

Rate

This is the baud rate to be used on the Master port. It must match the baud rate
setting used by the slave that will be connected to this Master port.

To maximize the port multiplexing capability of the gateway, it is recommended, if
possible, that you set the baud rate on the Master port and on the attached slave
as high as the slave can accommodate, up to 38,400; then set the baud rate for
the gateway slave ports and remote Master networks to a lower setting. This will
help prevent multiple Masters from overloading the response capability of the
single slave and the gateway.

Enter the baud rate as a value, shown in this list.

Baud Rate

Parameter Value

110

110

150

150

300

300

600

600

1200

12

OR

1200

2400

24

OR

2400

4800

48

OR

4800

9600

96

OR

9600

14,400

14,

114

OR

14400

19,200

19,

192

OR

19200

28,800

28,

288

OR

28800

38,400

38,

384

OR

38400

57,600

57

OR

576

115,200

115

OR

1152