Open loop ground water systems, Comfort alert, High speed – Envision Peripherals R-410A User Manual

Page 10

Advertising
background image

10

ENVISION RESIDENTIAL INSTALLATION MANUAL

Open Loop Ground Water Systems

Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control

valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize

mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat

exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 GPM of flow per ton

of cooling capacity is recommended in open loop applications.

Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending

on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of

sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.

Note: For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW2-Switch #2 to the

“WELL” position. (Refer to the table on page 28.) Slow opening/closing solenoid valves (type VM) are recommended to eliminate

water hammer.

Acc Com
Acc NC
Acc NO

1
2
3

C
R

P1

P3

SV

Solenoid

Valve

CC-GND

CC

CCHI

Comfort

Alert

Y1

Y2

Logic Board

Violet(3)

Blk(1)

Wht(4)

VM valve

Violet(2)

CC

SV

High Speed

Figure 9b: Open Loop Solenoid Valve Connection Option

Typical slow operating external 24V water solenoid valve

(type VM) wiring.

Figure 9a: Open Loop Solenoid Valve Connection Option

Typical quick operating external 24V water solenoid valve

(type PPV100 or BPV100) wiring.

Flexible

Duct Collar

Vibration

Absorbing Pad

P/T Plugs

Drain

Desuperheater

Connections

Auxiliary
Heater
Knockout

Low Voltage

to Thermostat

and Valve

Unit Supply

Aux. Heat Supply

Water Out

Water In

Shut Off Valves

Boiler Drains

For HX Flushing

Disconnects

(IfApplicable)

Rubber Bladder

Expansion Tank

Solenoid

Valve

Shut Off Valves

(to isolate solenoid

valve while acid flushing)

Strainer

Flow Control

Valve

(on outlet of

Solenoid Valve)

Compressor
Line Voltage

Figure 10: Open System - Groundwater Application

Note:

SW2-3 should be in the Comp “ON” position.