ENVISION RESIDENTIAL INSTALLATION MANUAL

Setting Fan Speed - ECM

ECM2 fan motors have a 12-speed selector dip switch on the logic board (SW1) and are factory set for optimum perfor-

mance. To change speeds, select the appropriate speeds on dip switch SW1. Consult the ECM2 fan performance table

below for specific airflow and switch information.

CAUTION: Disconnect all power before performing this operation.

Fan Performance Data - ECM

ECM2

1
2
3
4
5
6
7
8
9

10
11
12

SW1

On

Off

A 12-position DIP switch package on the control allows the airflow levels to be set for low, medium, and high

speed when using the ECM2 blower motor. Only three of the DIP switches can be in the "on" position.

The first "on" switch (the lowest position number) determines the low speed fan setting.

The second "on" switch determines the medium speed fan setting.

The third "on" switch determines the high speed fan setting.

The example to the right shows SW1 on the control board configured for the following NS042 airflow settings.

Low Speed Fan: 900 CFM

Medium Speed Fan: 1150 CFM

High Speed Fan: 1450 CFM

Single Speed

Dual Capacity

MAX

AIR FLOW DIP SWITCH SETTINGS

ESP

1

2

3

4

5

6

7

8

9

10

11

12

400

500

600

700

800

900

1000

1100

1200

L

M

H

400

500

600

700

800

900

1000

1100

1200

L

M

H

650

750

850

1000

1100

1200

1300

1400

1500

L

M

H

036

800

1000

1100

1300

1500

1600

1800

w/1hp*

L

M

H

650

800

900

1050

1150

1250

1350

1450

1550

L

M

H

042

800

900

1000

1200

1400

1600

1700

1850

2000

2200

2300

2400

w/1hp*

L

M

H

650

800

900

1050

1150

1250

1350

1450

1550

L

M

H

048

800

900

1000

1200

1400

1600

1700

1850

2000

2200

2300

2400

w/1hp*

L

M

H

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

5/30/06

Factory settings are at recommended L-M-H DIP switch locations

CFM is controlled within ±5% up to the maximum ESP

M-H settings MUST be located within boldface CFM range

Max ESP includes allowance for wet coil and standard filter

Lowest and Highest DIP switch settings are assumed to be L and H respectively

MAX

AIR FLOW DIP SWITCH SETTINGS

ESP

1

2

3

4

5

6

7

8

9

10

11

12

400

500

600

700

800

900

1000

1100

1200

L

M

H

650

750

850

1000

1100

1200

1300

1400

1500

L

M

H

038

800

1000

1100

1300

1500

1600

1800

w/1hp*

L

M

H

650

800

900

1050

1150

1250

1350

1450

1550

L

M

H

049

800

900

1000

1200

1400

1600

1700

1850

2000

2200

2300

2400

w/1hp*

L

M

H

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

5/30/06

Factory settings are at recommended L-M-H DIP switch locations

CFM is controlled within ±5% up to the maximum ESP

M-H settings MUST be located within boldface CFM range

Max ESP includes allowance for wet coil and standard filter

Lowest and Highest DIP switch settings are assumed to be L and H respectively

MODEL

022

0.50

026

0.50

0.75

030

0.50

036

0.50

0.75

042

0.50

0.75

048

0.50

MODEL

070

0.75

060

0.75

049

0.50

0.75

038

0.50

0.75

072

0.75

064

0.75