ENVISION RESIDENTIAL INSTALLATION MANUAL

Operation Logic Data

OPERATION LOGIC

HEATING

COOLING

FAN ON SL1 - IN ON

STG1

STG2

STG3

EMERG

STG1

STG2

SINGLE SPEED UNITS

Compressor

On

On

On

Off

On

On

-

-

ECM2 Normal

Med

High

High

High

Med

High

Low

-

ECM2 Dehumidify

Med

High

High

High

85% Med

85% High

Low

-

PSC

On

On

On

On

On

On

On

-

Rev Valve

Off

Off

Off

Off

On

On

-

-

Loop Pump

On

On

On

Off

On

On

-

On

DHW Pump

On

Off

Off

Off

On

On

-

-

Aux Heater

Off

Off

Staged

Staged

Off

Off

-

-

Secondary 1- Out

On

On

On

Off

On

On

-

-

Emerg LED

Off

Off

Off

On

Off

Off

Off

-

T-Stat Signal

Y1

Y1, Y2

Y1, Y2, W

W

Y1, O

Y1, Y2, O

G

-

DUAL CAPACITY UNITS

Compressor-Lo

On

Off

Off

Off

On

Off

-

-

Compressor-Hi

Off

On

On

Off

Off

On

-

-

ECM2 Normal

Med

High

High

High

Med

High

Low

-

ECM2 Dehumidify

Med

High

High

High

85% Med

85% High

Low

-

Rev Valve

Off

Off

Off

Off

On

On

-

-

Loop Pumps

On

On

On

Off

On

On

-

On

DHW Pump

On

On

Off

Off

On

On

-

-

Aux Heater

Off

Off

Staged

Staged

Off

Off

-

-

Secondary 1- Out

On

On

On

Off

On

On

-

-

Secondary 2- Out

Off

On

On

Off

Off

On

-

-

Emerg LED

Off

Off

Off

On

Off

Off

-

-

T-Stat Signal

Y1

Y1, Y2

Y1, Y2, W

W

Y1, O

Y1, Y2, O

G

-