General installation information, Moving and storage, Unit location – Envision Peripherals R-410A User Manual

Page 4: Installing vertical units, Safety considerations

Advertising
background image

4

ENVISION RESIDENTIAL INSTALLATION MANUAL

Moving and Storage

Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packag-

ing. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height

of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully

checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage,

removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is

noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.

Unit Location

Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have

enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical

and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air

to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after

the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for

a condensate drain trap and do not locate the unit above supply piping.

Care should be taken when units are located in

unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical

components.

Installing Vertical Units

Prior to setting the unit in place, remove and discard the compressor hold down

shipping bolt located at the front of the compressor mounting bracket.

Vertical units are available in left or right air return configurations. Top air dis-

charge vertical units should be mounted level on a vibration absorbing pad slightly

larger than the base to provide isolation between the unit and the floor. It is not

necessary to anchor the unit to the floor (see right).

Bottomflow units should be mounted level and sealed well to floor to prevent air

leakage. Bottomflow units require the supply air opening to be cut at least 1/2˝ larger

than the unit’s air outlet. Protect the edges of combustible flooring with sheet metal

over-wrap or other non-combustible material.

WARNING:

Before performing service or maintenance operations on a system, turn off main

power switches to the indoor unit. If applicable, turn off the accessory heater power switch.

Electrical shock could cause personal injury.

Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical

components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equip-

ment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters.

All other operations should be performed by trained service personnel. When working on heating and air conditioning equip-

ment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a

fire extinguisher available.

Safety Considerations

General Installation Information

Figure 1: Vertical Unit Mounting

2” Extruded
Polystyrene

Advertising