Unit operating parameters, Single speed models – Envision Peripherals R-410A User Manual

Page 35

Advertising
background image

35

ENVISION RESIDENTIAL INSTALLATION MANUAL

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

022-070

Superheat

022-070

Subcooling

Water Temp

Rise °F

Air Temp Drop

°F DB

1.5

133 - 148

205 - 225

17 - 26

10 - 14

18 - 22

18 - 22

3.0

129 - 144

185 - 205

20 - 29

7 - 11

8 - 10

18 - 22

1.5

139 - 154

280 - 300

8 - 11

8 -12

18 - 22

18 - 22

3.0

137 - 152

250 - 270

9 - 12

7 - 11

8 - 10

18 - 22

1.5

143 - 158

360 - 380

8 - 11

9 - 13

18 - 22

16 - 20

3.0

141 - 156

330 - 350

9 - 12

8 - 12

8 - 10

16 - 20

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

022-070

Superheat

022-040

Subcooling

048

Subcooling

060-070

Subcooling

Water Temp

Drop °F

Air Temp Rise

°F DB

1.5

73 - 79

279 - 304

7 - 13

2 - 6

11 - 15

4 - 8

7 -10

18 - 24

3.0

79 - 85

285 - 310

8 - 14

2 - 6

11 - 15

4 - 8

3 - 6

20 - 26

1.5

103 - 109

308 - 333

8 - 12

4 - 8

13 - 17

6 - 10

8 - 11

20 - 26

3.0

110 - 116

315 - 340

9 - 13

4 - 8

13 - 17

6 - 10

4 - 7

22 - 28

1.5

140 - 146

330 - 365

10 - 14

7 - 11

14 - 18

9 - 13

11 - 14

26 - 32

3.0

146 - 153

340 - 375

10 - 14

7 - 11

14 - 18

9 - 13

7 - 10

28 - 34

90

Entering Water

Temp °F

Heating -- No Desuperheater

30

Water Flow

GPM/Ton

Cooling -- No Desuperheater

50

70

50

70

Entering Water

Temp °F

Water Flow

GPM/Ton

Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.

Unit Operating Parameters

Single Speed Models

Advertising