ENVISION RESIDENTIAL INSTALLATION MANUAL

Green "POWER" LED - module has power
Red "TRIP" LED - Thermostat "Y" demand signal is present, but the compressor is not running.

Yellow "ALERT" LED

LED Description

Cause

Flash Code 1

Long Run Time

Eighteen consecutive hours of compressor run time

Flash Code 2

System Pressure Trip

Not applicable

Flash Code 3

Short Cycling

Compressor run time of less than 3 minutes on 4 consecutive cycles

Flash Code 4

Locked Rotor

Four consecutive compressor protector trips indicating compressor won't start

Flash Code 5

Open Circuit

"Y" thermostat demand signal with no compressor current

Flash Code 6

Open Start Circuit

"Y" thermostat demand signal with no current in the start circuit

Flash Code 7

Open Run Circuit

"Y" thermostat demand signal with no current in the run circuit

Flash Code 8

Welded Contactor

Current detected with no "Y" thermostat demand signal present

Flash Code 9

Low Voltage

Less than 17 VAC detected in control circuit

* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated.

* TRIP and ALERT LEDs flashing at the same time indicates control circuit voltage is too low for operation.

* Reset ALERT flash code by removing 24 VAC power from module.

* Last ALERT flash code is displayed for 1 minute after module is powered on.

Resetting Comfort Alert Codes
Alert codes can be reset manually by cycling power off and on to the Comfort Alert module. Alert codes will reset automatically if
conditions return to normal.

Flash Code Number

LED Description

Automatic Reset of Alert Codes

Flash Code 1

Long Run Time

Thirty "alert free" on and off cycles to reset automatically

Flash Code 2

System Pressure Trip

Not applicable

Flash Code 3

Short Cycling

Four "alert free" on and off cycles to reset automatically

Flash Code 4

Locked Rotor

Four "alert free" on and off cycles to reset automatically

Flash Code 5

Open Circuit

One "alert free" on and off cycles to reset automatically

Flash Code 6

Open Start Circuit

One "alert free" on and off cycles to reset automatically

Flash Code 7

Open Run Circuit

One "alert free" on and off cycles to reset automatically

Flash Code 8

Welded Contactor

One "alert free" on and off cycles to reset automatically

Flash Code 9

Low Voltage

Resets when voltage rises above 19 VAC

* Reset ALERT flash code by removing 24 VAC power from module.

Comfort Alert Flash Codes

Microprocessor Control (cont.)

Compressor Monitoring/Comfort Alert

The comfort Alert displays abnormal compressor conditions through a unique flash code and communicates the conditions to the

heat pump microprocessor control. The heat pump microprocessor will determine which fault to act on and ignore. Fault codes 2 (sys-

tem pressure), 4 (locked rotor), 6 (open start circuit), and 7 (open run circuit) will result in a lockout. All other fault codes are passive.

All compressor alerts are displayed on the module by flashing the yellow Alert LED a specific number of times consecutively followed

by a pause, and then repeated. The number of consecutive flashes or “Flash Code” correlates to a specific abnormal condition. The

red “TRIP” LED means there is a thermostat demand signal “Y” present but the compressor is not running. The green “POWER” LED

means the module has power.