Troubleshooting, Standard microprocessor controls, Refrigerant systems – Envision Peripherals R-410A User Manual

Page 38: Led definitions and diagnostics

Advertising
background image

38

ENVISION RESIDENTIAL INSTALLATION MANUAL

Troubleshooting

Standard Microprocessor Controls

To check the unit control board for proper operation:

1) Disconnect thermostat wires at the control board.

2) Jumper the desired test input (Y1, Y2, W, O or G) to the R terminal to simulate a thermostat signal.

3) If control functions properly:

• Check for thermostat and field control wiring (use the diagnostic inputs mode).

4) If control responds improperly:

• Ensure that component being controlled is functioning (compressor, blower, reversing valve, etc.).

• Ensure that wiring from control to the component is functioning (refer to the LED Definition table below and use the

diagnostic outputs mode).

• If steps above check properly, replace unit control.

Refrigerant Systems

To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the

change in temperature on the air side as well as the water side to the tables on pages 35-36. If the unit’s performance is not

within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and super-

heat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to

the refrigerant charge may be necessary.

Note: Refrigerant tests must be made with desuperheater turned “OFF”. Verify that air and water flow rates are at proper

levels before servicing the refrigerant circuit.

LED

NORMAL

DISPLAY MODE

DIAGNOSTIC MODES

CURRENT

FAULT STATUS

INPUTS

OUTPUTS 1

OUTPUTS 2

Field Selection DIPS

SW2-

1 On

SW2-

1 Off

SW2-

1 NA

SW2-

1 NA

SW2-

1 NA

SW2-

6 On

SW2-

6 On

SW2-

6 Off

SW2-

6 On

SW2-

6 Off

SW2-

7 On

SW2-

7 On

SW2-

7 On

SW2-

7 Off

SW2-

7 Off

Drain

Drain Pan Overflow

Lockout

Drain Pan Overflow

Y1

Compressor

(On or Low)

Blower

Low

Water Flow

FP Thermistor (Loop

<15º F, Well<30ºF)

Lockout

FP Thermistor (Loop

<15º F, Well<30ºF)

Y2

Compressor

(On or High)

Blower

Medium

High

Pressure

High Pressure >600

PSI Lockout

High Pressure >600

O

Reversing Valve

Blower

High

Low

Pressure/

Compressor

Low Pressure <40

PSI Lockout or

Comfort Alert

Low Pressure <40

or Comfort Alert

G

Fan

Aux Heat 1

Airflow

ECM2 RPM <100

RPM

ECM2 RPM

<100 RPM

W

DHW Pump

Aux Heat 2

Status

Microprocessor

Malfunction

Not Used

SL1

Loop Pump(s)

Aux Heat 3

DHW Limit

HWL Thermistor

>130º

HWL Thermistor

>130°F

Not Used

Aux Heat 4

DHW Off

DHW Pump

Switch Off

DHW Pump

Switch Off

LED Definitions and Diagnostics

Standard Microprocessor