EMI S2HB User Manual

Page 10

Advertising
background image

www.enviromaster.com

10

multi-zone Heat Pump Condensing units

• A P-trap is recommended when the suc-

tion riser is equal to or greater than 20

feet in height.

• When the condenser is installed above

the evaporator, the P-trap will help the

return of oil back to the compressor.

• The placement of the P-trap should be at

the halfway mark of the suction riser. For

example if the suction riser is 30 feet tall

then a P-trap is recommended at the 15 foot

mark of the suction riser (see Figure #1).

• A P-trap may be fabricated using;

(2) street elbows and (2) regular elbows.

A prefabricated trap may be purchased

from a Wholesaler or Distributor how-

ever the trap should be shallow as the:

(4) elbow configuration. Each elbow is

approximately 2 equivalent feet. One P-

trap is equal to approximately 8 equiva-

lent feet.

P-trAP InStAllAtIon

Figure #1