multi-zone Heat Pump Condensing units

The use of the superheat method is highly

recommended for field charging or checking

the existing refrigerant charge in a system.

Because each installation is different in terms

of indoor air flow, refrigerant line length, etc..,

the factory charge may not be correct for

every application. To assure the best perfor-

mance from the air-conditioner, the refrigerant

charge should be checked and adjusted, if

need be, on each installation.

For proper superheat readings, a standard

low-side refrigerant gauge and an accurate

thermometer are needed. A mercury or

stem-type thermometer is not adequate

for suction-line temperatures. We recom-

mend electric thermocouple thermometers

(available at most refrigeration wholesal-

ers); however an accurate remote-bulb

thermometer can be used. When mea-

suring the line temperature, be sure the
thermometer is well insulated to assure

accurate measurements. The chart below

gives superheat values at various outdoor

temperatures. Allow at least 5 minutes run-

ning time between charge adjustments for

the unit to stabilize.

The S & T series (S2HB, T2HB, T3HB &

T4HB) have manifold access points on

each of the service valves for the high and

low pressures in cooling mode. There is an

additional “common suction” access point

above each service valve set to provide low

pressure access in the heating mode as both

service valves are at high side pressure.

Field CHarging

mulTi-Zone HeaT PumP reFrigeranT CHarge TaBle

Circuit

Capacity Btuh

Evaporator

Pairing

Line

Chg/ft

Line

Length

Line

Adjust

Factory

Charge

Total

Charge

9000

WLH09

CAH12

UNH09

0.25 oz

10 ft

25 ft

50 ft

3 oz

6 oz

13 oz

42

45 oz

48 oz

55 oz

12000

WLH12

CAH12

UNH12

0.25 oz

10 ft

25 ft

50 ft

3 oz

6 oz

13 oz

46

49 oz

52 oz

59 oz

18000

WLH24

CAH24

UNH24

0.56 oz

10 ft

25 ft

50 ft **

6 oz

14 oz

28 oz **

63

86 oz

94 oz

108 oz

24000

WLH24

CAH24

UNH24

0.56 oz

10 ft

25 ft

50 ft

6 oz

14 oz

28 oz

80

86 oz

94 oz

108 oz

** Any 18,000 Btuh circuit with more than 87 feet of tubing (> 112 oz of total refrigerant charge) requires a 25W

wrap around Crankcase Heater.

imPorTanT noTeS:

1. To find the charge adjustment and system charge for any evaporator and

tubing length:

Line Adjustment = (Line Chg/Ft) x Line Length
System Total = Factory Charge + Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.
3. U

se R22 refrigerant.